GENERAL SANITATION INSPECTION REPORT FOR JEFFERSON HIGH SCHOOL PERFORMED MARCH 19, 2001

15 B Water damaged ceiling tiles in classroom D 5.

5E Ceiling vents not clean in classroom D 6.

18A Termite activity in classroom C 5.

18A Ant infestation throughout the school.

1 7J Soap not provided in men’s toilet rooms throughout the school.

5B Severe problem with smoking in toilet rooms [especially bad in men’s toilet rooms], ashes on almost all student toilets and air is thickly contaminated with smoke. Ventilation Systems for toilet rooms do not appear to be adequate.

5B Excessively hot in classroom C 1.

5E Ceiling ducts not clean in classroom C 18 & C 19.

5E Classroom C 18 & C 19 is very dusty.

5E Air vents in hallway of C section not clean.

 Water damaged ceiling tile in classroom C 13.

6A Carpets do not appear to be cleaned at an acceptable frequency. A review and follow-up of the written housekeeping schedule may be necessary.

5A Classroom A 26 has discoloration on carpet, that appears to be related to a mold/mildew problem.

1 5B Water damaged ceiling tile in classroom A 1.

19D Drinking fountains throughout the school are not clean. (they appear to not have been thoroughly cleaned for days, possible weeks}

SE Ceiling not clean around vents in classroom A 20.

1 5B Water damaged ceiling tiles in classroom A 20.

5E Ceiling vents not clean in toilet rooms.

1 5B Water damaged ceiling tiles in hallway outside of ladies toilet room in A section.


 Sagging ceiling tiles in room A 16.

1 8B Evidence of rodent activity beneath the sink in the teachers lounge in A section.

 Water damaged ceiling tiles in classroom A 5.

1 5B Classroom C 5 and A 5 have water leaks around back door.

 Water damaged ceiling tiles in hail by classrooms A 13 and A 8.

18C Door to outside by cafeteria not tightly sealed across bottom.

17G More thorough toilet room cleaning needed throughout school.

5E Ceiling vents not clean in toilet rooms in the back of A section.

18B Evidence of rodent activity in classroom A 12.

lOB Sewer gas odor in staff toilet rooms in A section.

18C Door to outside by ramp leading to B section not tightly sealed across the bottom.

 Water damaged ceiling tiles in hail of B section.

5E Ceiling vent not clean in classroom B 14.

1 5B Water damaged ceiling tiles in classroom B 14 and by entrance to B 12.

1 7G Floor tiles in bad repair in staff toilet rooms in B section.

1 7J Soap and covered trash containers not provided in staff toilet rooms.

15E Plastic cover needed over science sink in the center of classroom B 5.

I IA Outlet safety covers needed on outlet wall strips in classroom B 5.

1 8C Door to outside not tightly sealed in classroom B 10.

lOB Faucet leaking at art sink in classroom B 11.

18C Door to outside not tightly sealed in classroom B 6.

 Water damaged ceiling tiles in Music room, room D 8..

SE Ceiling tiles very dirty, especially around ceiling vents in Music room, room D 8.

17J Soap not provided in boys locker room, at the hand sinks by the toilet facilities.

I SB Floor tiles in bad repair in the boys locker room.

15E Vinyl torn on massage tables in training room.

1 5B Water damaged ceiling tiles in hall by gymnasium.

17G Floor/wall tiles missing in girls toilet room by cafeteria.

I SB Ceiling in bad repair by entrance to girls toilet room by cafeteria.

 

INSPECTION REPORT FOR JEFFERSON HIGH SCHOOL FOOD SERVICE PERFORMED ON MARCH 19, 2001

There were no violations of the WV Food Service Rules noted at the time of the evaluation.

 

Click for School System's description of physical condition of buildings

 

GENERAL SANITATION INSPECTION REPORT FOR JEFFERSON HIGH SCHOOL PERFORMED MAY 25, 2001

I 7J Soap dispensers not provided in all student toilet rooms.

1 7G Faucets in bad repair in staff toilet rooms in B section

I 5B Floor/wall molding in bad repair in girls toilet room in section A

15B Ceiling in bad repair in boys and girls locker rooms off of gymnasium.

19C Mixing faucets not provided in boys toilet room off of locker room by gymnasium.

8B Inadequate light in boys shower room.

1 7G Tile cracked in boys shower room.

14B Storage area beside auditorium (by the toilet rooms) not clean and organized.

18C Doors to outside of the building throughout the school not tight fitting ( rodent and insect proof).

SB Smoking in student toilet rooms (much improvement from inspection performed on March 19th but still very much a problem) must be permanently addressed towards providing a sanitary atmosphere in these toilet rooms.

17J Soap and covered trash containers not provided in staff toilet rooms. I 7G Floor/wall tiles in bad repair in several toilet rooms.


Click for School System's description of physical condition of buildings

 


GENERAL SANITATION REPORT FOR CHARLES TOWN JUNIOR HIGH SCHOOL PERFORMED MARCH 8, 2001

 Broken floor tiles in hallway.

I 8C Door to outside not tightly sealed in P. Warner’s computer lab.

18C Door to outside not tightly sealed in room 57 and room 58.

1 5B Water damaged ceiling tiles in room 58.

SB Air conditioning ducts cleaned? There was an odor problem early in the school year that diminished after the air conditioning system was shut down..

lOB Faucet dripping from hand sink in boys toilet room across from cafeteria.

19C Hot water not provided (waterline is shut off) to one hand sink in girl’ toilet room across from cafeteria.

18C Door not tightly sealed across bottom H.Tabeek’s classroom.

170 Toilet dividers in bad repair in boys toilet room in A section.

1 5B Water damaged ceiling tiles in music room.

 Serious water damage ceiling tiles in art room (water laying on light shields) [room 40).

8F Light shields not provided in boys locker room.

1 5G Some of the gym lockers are in bad repair in the boys locker room.

lOB Showerhead dripping in boys locker room.(first one on left).

I 5B Floor in bad repair in toilet room in boys locker room.

I7J Paper towel dispenser empty in toilet room in boys locker room.

lOB Showerhead dripping in girls locker room (second on right).

6A Ceiling vent not clean in girls shower room.

I 7P Covered trash containers (for sanitary disposal) not provided in toilet room in girls locker room.

I OB Faucets leaking in boys toilet room across from room 30.

I5B Floor tiles in bad repair in both boys and girls toilet rooms across from room 30.

 Water damaged ceiling tiles along outside wall in classroom #11 and ff13.

11A Smoke detector not working in room # RI.

lOB Faucet leaking in teachers work room (close to exit to portable class rooms).

I SB Missing floor tiles in storage room off of Mr. Starkeys room.

 Water damaged ceiling tiles in storage room off of Mr. Starkeys room.

 Floor/wall molding missing in room # 25.

 

INSPECTION REPORT FOR CHARLES TOWN JUNIOR HIGH SCHOOL PERFORMED ON MARCH 8, 2001

6-201.11 Floor in toilet room in bad repair.

4-501.110 Dish washing machine rinse water temperature not high enough (machine should register at least 180° F with a plate temperature of at least 165° F; the actual machine reading was 174° F with a plate temperature of 162° F)

 

Click for School System's description of physical condition of buildings

 


GENERAL SANITATION INSPECTION REPORT FOR HARPERS FERRY JUNIOR HIGH SCHOOL PERFORMED ON MARCH 30, 2001

I 5B Water damaged ceiling tiles in music room.

1 7G More thorough bathroom cleaning needed, especially floors along walls and around toilets.

1 11A Sagging ceiling tiles in library.

14A More storage space needed in library.

11 A Carpet bunching up in library.

 Water damaged ceiling tiles in upper hallway.

19C Mixing faucets not provided in staff toilet rooms on second floor.

1 5B Water damaged ceiling tile in nurses room..

8F Light shield broken in boys toilet room by cafeteria.

1 SB Water damaged ceiling tiles in girls locker room.

lOB Water leaking from shower head in girls shower room.

1 5B Ceiling tiles in bad repair in boys locker room.

1 7J Soap not provided in toilet room off of boys locker room.

1 8C Door to outside in machine shop not tightly sealed across the bottom.

15 Paint peeling from ventilation ducts in ceiling of machine shop.

1 7A With the addition of eight classrooms in portable buildings behind, the school does not have adequate toilet facilities for the schools population.

158 Water damaged ceiling tiles in hall leading to cafeteria.

 

INSPECTION REPORT FOR HARPERS FERRY JUNIOR HIGH SCHOOL FOOD SERVICE PERFORMED ON MARCH 30 200!

6-201.11 Paint is peeling off of wall over three compartment sink.

4-101. 111 D Counter top by steam table not cleanable.


Click for School System's description of physical condition of buildings

 

GENERAL SANITATION INSPECTION REPORT FOR SHEPHERDSTOWN JUNIOR HIGH SCHOOL PERFORMED MARCH 29, 200l

1 5B Water damaged ceiling tile by door in classroom if 22 and in classroom if 23.

1 SB Floor tile cracked by outside exit near music room (# 24).

1 5B Floor tile cracked in hallway by classroom # 1.

 Ceiling tile sagging in classroom # 21.

 Water damaged ceiling tile in front corner of classroom if 1.

1 5B Concrete block missing in wall beneath chalk board in classroom if I.

l SB Water damaged ceiling tile in kitchen area of FACS room.

1 SB Floor in bad repair (not cleanable) in girls toilet room across from gymnasium.

l 8C Door to outside in machine shop not tightly sealed across the bottom.

5E Ceiling vent not clean in boys toilet room by gymnasium.

l 5B Wall tiles in bad repair (cracked, not cleanable) in boys toilet room by gymnasium.

5E Ceiling vent missing cover in hallway by the entrance to the machine shop.

 Floor/wall tiles cracked in toilet rooms off of locker rooms.

8F Light shield broken in girls locker room.

11A Mirror cracked in boys toilet room off of locker room.

18C Door to outside off of boys locker room not tightly sealed across the bottom.

8F Light shields not provided in equipment storage room off of gymnasium.

l70 Handle broken on privacy door to disability access toilet in girls toilet room across from principals office.

1 9D Inadequate water pressure at drinking fountain in hallway across from principals office.

 Wall in bad repair in stairway leading to art room.

 Paint peeling from ceiling in art room, art storage room, and office off of art room.

 Hole in ceiling in storage room off of art room exposing insulation.

1 7G Tile missing by urinal closest to wall in boys toilet room by principals office.

170 Handle missing on privacy door to disability access toilet in boys toilet room by principals office.

1 LA Broken window glass in classroom if 14.

8F Two light shields missing in computer lab.

1 5B Water damaged ceiling tile in computer lab.

 

INSPECTION REPORT FOR SHEPHERDSTOWN JUNIOR HIGH SCHOOL FOOD SERVICE PERFORMED MARCH 22, 2001

6-201. 1 1 Ceiling tiles discolored around hood.

4-102.111 Utensil holders on serving line in bad repair.

4-601.11 1 Interior of walk-in refrigerator no clean ( white mold-like growth).

6-201.12 Wall around duct in storeroom not sealed.

5.501. 110 Inadequate dumpster capacity for garbage storage.


Click for School System's description of physical condition of buildings

 


GENERAL SANITATION INSPECTION REPORT FOR BLUE RIDGE  ELEMENTARY SCHOOL PERFORMED MARCH 27, 2001

 Water damaged ceiling tile in toilet room in classroom if 14.

1 IA Over stocked shelf over coat rack in classroom # 14.

6A Ceiling tiles not clean around air ducts in classrooms # 14 & if 6.

1 SB Water damaged ceiling in the larger portable classroom.

I4A Toilet room not operational, used for storage, in the larger portable classroom.

I 8C Door to outside not tightly sealed in the portable classroom with the brick facing.

 Water damaged ceiling tiles in classrooms # 1& # 4.

18A Ant activity in cafeteria dining area.

1 5B Ceiling water damaged by vent, in boys toilet room in upper hallway near cafeteria.

1 SB Water damaged ceiling tiles in hallway leading to cafeteria.

 Missing ceiling tiles, exposed insulation in classroom # 7.

1 8A Food products stored in classrooms should be stored in glass, metal, or plastic air tight containers.

I5B Water damaged ceiling tiles by entrance to classroom # 6.

 Paint peeling from brick wall in boys toilet room by gymnasium.

l7J Soap not provided in boys toilet rooms.

19D Drinking fountain not clean by gymnasium.

l5B Paint peeling from wall in girls toilet room by utility room with chlorinator.

1 SB Ceiling tiles missing, water damaged in boys toilet room by utility room with chlorinator.

1 7G Urinal privacy barrier badly corroded in boys toilet room by utility room with chlorinator.

SE Ceiling vent not clean in classroom ft 4.


1 8C Door to outside not tightly sealed in library.

 Water damaged ceiling tiles in library and office off of library.

1 SB Missing ceiling tile and water damaged ceiling tile in hallway by office.

15E Window blinds in bad repair in classroom # 24.

1 5B Water damaged ceiling tiles in classroom ft 24.

18C Door to outside (old main entrance) not tightly sealed across the bottom.

18C Door to outside (to staff parking lot) not tightly sealed across the bottom.

1 5B Water leaking onto electrical conduit and light fixtures in classroom if 21.

lOB Water leaking from faucet in sink in classroom # 21.

SE Heating units on wall not clean in classroom if 21.

1 8C Door to outside by dumpster not tightly sealed across bottom.

 Water damaged ceiling tile in hallway by classroom # 32.

 

INSPECTION REPORT FOR BLUE RIDGE ELEMENTARY SCHOOL FOOD SERVICE PERFORMED MARCH 27, 2001

4-101.111 Laminate in bad repair on front of serving line.


Click for School System's description of physical condition of buildings

 


GENERAL SANITATION INSPECTION REPORT FOR NORTH JEFFERSON ELEMENTARY SCHOOL PERFORMED MARCH 13, 2001

4C Dumpster lid broken, laying on the ground.

 Floor in bad repair in women’s staff toilet room

lOB Seal appears to be leaking on toilet in women’s staff toilet room.

19C Mixing faucet not provided in staff toilet rooms.

19D Drinking water dispenser not clean in staff lounge (west end of building)

6A Microwave oven in classroom #25 not clean

I 5B Tile broken-up along back wall in classroom if 6.

1 G & I E Cat in classroom #19, does cat have up to date rabies vaccination? The room smells like a dirty litter box.

SE Older wall heating units not clean

l 7G More thorough cleaning needed in toilet rooms.

6A More storage area needed for janitorial supplies, some are being stored in the hallway.

 Hole in ceiling tile in hallway leading to classrooms #30 and ff31.

I 7J Paper towels not provided in boys toilet room on west end of building.

5G Panel off of heat unit in art room, appears to be malfunctioning.

8 F Unshielded light fixture over ice cream freezer.

5 E Air ducts not clean in gym.

19 D Water fountain not clean in gym

6 A Acoustical wall panels not clean in gym.

18 C Door to outside not tightly sealed across the bottom in gym.

 Water damaged ceiling tile in computer room.


1 SC Door to outside across from computer lab not tightly sealed across the bottom.

18 C Door to outside not tightly sealed across the bottom in classroom # 10.

I S B Floor tile in bad repair and wall tile cracked in boys toilet room in the east end of building.

5 E Ceiling vents not clean in classroom if 4. (Especially bad over activity rug)

18 A All food products ( animal and human) stored in classrooms must be stored in air tight metal, glass or plastic containers to prevent insect and rodent infestation.

11 A Glass broken on door in hallway by large fish tank.

 

INSPECTION REPORT FOR NORTH JEFFERSON ELEMENTARY SCHOOL FOOD SERVICE PERFORMED MARCH 13, 2001.

3-302.11 Raw hamburger stored over uncovered dishes of jello.

3.401. 11 Temperature recording logs not kept.

6-501.14 Ceiling vent over dish machine not clean.


Click for School System's description of physical condition of buildings

 


GENERAL SANITATION INSPECTION REPORT FOR PAGE JACKSON ELEMENTARY SCHOOL  PERFORMED MARCH 15, 2001

6A Floors in kindergarten toilet rooms not thoroughly clean.

I 7G Urinal stall divider in bad repair in men’s toilet room.

19C Mixing faucets not provided in some of the toilet rooms in the school

1 9C Hot water not provided in student toilet rooms (it is turned off due to concern about hot water burns)

I5B Water damaged ceiling tile from ceiling leaks in MMI classroom.

1 SB Water damaged ceiling tiles from ceiling leaks in girls toilet room near cafeteria.

1 8C Door to outside not tightly sealed in hallway used for new book storage.

l4A More storage space needed for classroom supplies.

I5B Water damaged ceiling tiles in classroom # 17, if 20 & Ms. Potters’ room.

17G Floor/wall molding in bad repair in music room.

 

INSPECTION REPORT FOR PAGE JACKSON ELEMENTARY SCHOOL FOOD SERVICE PERFORMED MARCH 15, 2001

6-201.11 Water damaged ceiling tile in storeroom.

5-205.15 Mop sink water faucet leaking.

4-501.11 Excessive ice build-up in walk in freezer.

 

Click for School System's description of physical condition of buildings

 


GENERAL SANITATION INSPECTION REPORT FOR RANSON ELEMENTARY SCHOOL PERFORMED MARCH 28, 2001

19C Hot water for hand washing not provided in staff toilet room by cafeteria.

19C Hot water not provided for hand washing in student toilet rooms in main hallway.

1 SB Paint peeling from wall in girls toilet room by cafeteria.

5E Filter not clean on window unit air conditioner in Ms. Schnablys’ classroom.

I SB Ceiling tile missing by door to boys toilet room by cafeteria.

3A Turtles in Ms. Marcums’ classroom require that a written plan be provided and implemented for proper sanitary handling and hand washing procedures.

I SB Water damage on ceiling around vent in hallway outside Ms. Marcums’ classroom.

SF Light shield missing in room used for storage of ice cream and popcorn makers.

1 SB Water damaged ceiling tiles leading to gymnasium.

I 8C Door to outside not tightly sealed in Pre K classroom.

I SB Water damaged ceiling tiles by coat hooks in Ms. Thompsons’ classrooms and in Ms. Toothmans’ classroom.

18C Door to outside not tightly sealed in Ms. Costellos’ classroom.

6A Utility sinks in maintenance closets not clean.

 Loose ceiling tile in boys’ toilet room leading to gymnasium.

 Water damaged ceiling tiles in Councilors office.

6A Ceiling not clean in gymnasium by basket ball net closest to the music room.

I 8C Doors to outside in gymnasium not tightly sealed across the bottom.

8F Damaged light shield in Mr. Sherwoods’ classroom.

4 portable classrooms.


INSPECTION REPORT FOR RANSON ELEMENTARY SCHOOL FOOD SERVICE PERFORMED MARCH 28, 2001

6-201.1 I Paint peeling from wall over dish machine.

6-201.11 Floor/wall molding loose .around steam kettle drain

6-201. 1 1 Wall in bad repair, plaster broken up and not sealed around the plumbing, below the dish machine.


Click for School System's description of physical condition of buildings

 


GENERAL SANITATION INSPECTION REPORT FOR SHEPHERDSTOWN ELEMENTARY SCHOOL PERFORMED MARCH 26, 2001

18A Food stored in classrooms should be stored in metal, glass, or plastic air tight containers.

I SB Water damaged ceiling tiles over coat hooks in classroom if 11 & #8.

I4A Toilet room used for book storage in classroom ft 9.

I 5B Water damaged ceiling tiles in classroom #9.

14A Cabinet needed for sanitary storage of food in classroom #9.

14A Laminating machine stored in hallway.

1-5B Ceiling tiles in hallway by lockers badly discolored.

14A More organization of teaching supplies needed in Ms. Lawrences’ classroom.

I SB Hole in ceiling tile by vent in Ms. Lawrences’ classroom.

1 8C Door to outside not tightly sealed across bottom in library & in hallway leading to playground.

I 7G More thorough floor cleaning needed in student restrooms along the floor/wall

junctions.

I 5B Material covering ceiling in gymnasium loose [coming off in patches], not cleanable.

5E Heating units [wall units] in gymnasium not clean and in bad repair.

1 5B Floor tile missing in gymnasium.

 Floor/wall molding missing in gymnasium.

1 SB Water damaged ceiling tile by electrical panel in storage room off of gymnasium.

I5B Floor! wall tile cracked in boys toilet room in back of school.

SE Exposed insulation visible in Ms. Walters classroom ceiling vent.

5A Several classrooms have vents that are covered with tape.


 Floor/wall molding missing in classroom # 19.

 

INSPECTION REPORT FOR SHEPHERDSTOWN ELEMENTARY SCHOOL FOOD SERVICE PERFORMED MARCH 26, 2001

6-501.12 Ceiling vent not clean in storage room over freezer.

4-602.13 Ice maker filter not clean.

6-50 1.11 Water damaged ceiling tile over 3 door refrigerator not accurate.

6-501.11 Loose ceiling tile over 3 door refrigerator.

4-203.11 Thermometers on the two 3 door refrigerators not accurate.

4-101.1 ID Wood shelves for cleaning supplies not sealed [paint, varnish, polyurethane, etc.]


Click for School System's description of physical condition of buildings

 


GENERAL SANITATION INSPECTION REPORT FOR C.W. SHIPLEY ELEMENTARY SCHOOL PERFORMED MARCH 14, 2001

17G Toilet room fixtures not thoroughly cleaned (base of toilets and hand washing sinks).

1 SB Water damaged ceiling tiles in staff toilet rooms.

IOA Mixing faucets not provided in staff toilet rooms.

17G Floors not thoroughly clean in staff toilet rooms.

 Water damaged ceiling tiles in kindergarten.

I5B Water damaged ceiling tiles in hallway off of kindergarten.

SE Ceiling vents not clean in classroom if 10.

 Water damaged ceiling tiles in classroom #10.

 Ceiling tile loose over coat hooks in classroom #9.

 Ceiling tile not in place (exposed insulation) in classroom ft 11.

1 SB Water damaged ceiling tiles around ceiling vent in room # 11.

l4A Inadequate room for storage of school supplies (possibly some supplies that are no longer used could be discarded).

1 5B Water damaged ceiling tiles in hall immediately above entrance to classroom #13.

18C Door to outside leading to parking lot not tightly sealed across bottom.

6A Classroom floors do not appear to be receiving regular, thorough cleaning.

6B Upon request, received a copy of the schools cleaning schedule. Could it be adjusted to allow for more thorough floor and toilet room cleaning ? (Ex. 11:45-1:20 help students dump lunch trays, couldn’t teachers help with this? Then toilet rooms could be cleaned during the day, since they are cleaned only at 6 PM and often the school is used late in the evening. Also, on one schedule 1 hour is allotted to vacuum 4 rooms and on another schedule 25 minutes allotted for vacuuming 7 classrooms and wet mopping the modular class room floor).

19D Drinking fountains not clean.

1 9G Interior of icemaker not clean.

1 5B Water damaged ceiling tile in computer lab.

18C Door to outside not tightly sealed in classroom # 20, #21 & if 24.

I 8C Door seal in bad repair in room if 18.

1 SB Water damaged ceiling tiles in classroom # 24 & ft 27.

19F Cup dispensers not used in classroom # 24.

 Loose ceiling tile in classroom # 25.

ISA Ant activity along wall in room ft 27.

6A Sink and counter not clean in room # 28.

17J Soap not provided in boys’ toilet room.(end of building closest to the basket ball court)

5E Ceiling vent not clean in boys toilet room.(end of building closes to the basket ball court)

1 8C Doors to the outside leading to the basket ball hoops not tightly sealed across the bottom.

l7G Floors not clean in toilet rooms by gym.

19D Water fountain in gym not clean.

SE Exposed insulation around air duct return in portable class room.

1 SB Floor tile cracked in gym along wall.

1 SB Broken ceiling tiles along serving line in kitchen.

 

INSPECTION REPORT FOR C.W. SHIPLEY ELEMENTARY SCHOOL FOOD SERVICE PERFORMED MARCH 14, 2001

6-202. iS Back screen door not tightly sealed across bottom.

6-201.1 1 Wall tile cracked behind 2 vat sink.

4-201.1 1 More freezer storage space needed.

 

Click for School System's description of physical condition of buildings

 

SCHOOL SYSTEM LETTER CONCERNING LEAD & PESTICIDES AT SOUTH JEFFERSON ELEMENTARY SCHOOL

 

June 5, 2001

Dear Parents/Guardians:

As many of you know, there were a number of questions raised by parents and staff regarding the water quality and other health concerns at South Jefferson Elementary School As a result of these questions, several things have been done that we believe answer many of the questions presented. We would like to use this opportunity to update you and to let you know of projects that should be completed this summer.

The following has occurred:

The Jefferson County Health Department, the Regional Office of the West Virginia Health Department, the West Virginia University Extension Service - Jefferson County Office, the West Virginia Department of Agriculture and administrative staff from the Jefferson County Board of Education Office have been involved in the assessment process.

All water tests required by the West Virginia Health Department have continued on a regular basis and currently meet standards.

The West Virginia Department of Agriculture tested the soil for pesticides with no findings.

Reviews of aerial photos of the land taken prior to construction of the school indicated that the land was used as pasture. Research did not indicate that the land was used in a manner that would cause concern.

Bottled water was provided.

The water treatment plant has been upgraded as per recommendation by the West Virginia Department of Health and is currently in operation with the new treatment system.

The system is flushed daily at each point where consumption may occur.

Summer plans include:

          An assessment of the transformer by Allegheny Power.

          Pipes and fixtures replaced in classrooms where higher than normal lead levels have occurred in the past.

We want to assure you that currently water tests indicate that all levels meet approved standards. The activities planned for the summer are being completed only as a precaution and to assure that elevated lead levels do not occur in the future. Much has been learned by this process and, as a result, I believe that there will be better communication among the agencies.

All reports of tests administered this year are available in the Principal*s Office. Mrs. VanCamp will be glad to share those with you. Questions that cannot be answered at the school can be directed to Beverly Hughes, Associate Superintendent (728-9228), John Norman, Coordinator of Facilities and Maintenance (728-9215) or George Frame, Director of Support Services (728-9241).

Sincerely,

Beverly Hughes

Associate Superintendent

 


GENERAL SANITATION INSPECTION REPORT FOR SOUTH JEFFERSON ELEMENTARY SCHOOL PERFORMED APRIL 13, 2001

I SB Carpet in library is shredding at seams.

 Tile is broken up by HVAC system in art room.

1 IA Shelves over coat hooks overburdened in Ms. Mahoney’s classroom.

I IA Ceiling tile not tight fitting over sink in Ms. Mahoney’s classroom.

6A Light shield not clean in Ms. Woodburn’s classroom.

I 7G More thorough toilet room cleaning needed, especially floors.

I lA Ceiling tile not tight fitting in Ms. Batson’s classroom.

ISB Water damaged ceiling tiles in classroom if 7.

11A Ceiling tile not tight fitting (exposed insulation) in classroom # IS.

SE Filter not clean in wall HVAC system in Ms. Kees’ classroom.

 Water damaged ceiling tiles over sink in Ms. Kees’ classroom.

l5B Water damagçd ceiling tile in Ms. Cloud’s classroom.

19F Cup dispenser not used in Ms. Fincham’s classroom.

 Water damaged ceiling tiles in Ms. Fincham’s classroom.

4B Inadequate garbage storage facilities.

I 1A Ceiling tile not tight fitting in Ms. Greenfields’ classroom.

I 1A Shelves over coat rack overburdened in Ms. Greenfields’ classroom.

I IA Ceiling tiles not tight fitting in Ms. Whittingtons’ classroom.

8F Light shield missing in classroom # 14.

1 1A Ceiling tile not tight fitting in classroom # 14.

1 7G Floor not cleanable in boys toilet room where old toilet dividers were anchored.

1 7J Two soap dispensers missing in girls toilet room on south end of building.

I SB Floor tiles cracked in hallway along intersection leading to Ms. Clouds’ classroom.

I 5B Floor/wall molding loose and in bad repair in numerous classrooms.

6A Portable stage not clean in music room.

11 A Shelf over coat hooks overburdened in classroom # 24.

I 5B Water damaged ceiling tile around smoke detector in hallway by Ms. Clouds’ classroom.

170 Boys toilet room door not tight fitting on south end of building.

6A Carpet not clean in classroom if 20 and #21.

1 1 A Ceiling tile not tight fitting in classroom #20.

1 1A Shelf over coat rack overburdened in Mr. Marmorellas’ classroom.

 

INSPECTION REPORT FOR SOUTH JEFFERSON ELEMENTARY FOOD SERVICE PERFORMED ON APRIL 13, 2001

Inadequate freezer storage space provided for current food ordering system.


Click for School System's description of physical condition of buildings

 


GENERAL SANITATION INSPECTION REPORT FOR WRIGHT DENNY ELEMENTARY SCHOOL PERFORMED ON MARCH 9, 2001

lOH Mop sink not provided for kitchen and cafeteria area.

 Water damaged ceiling tile in hallway between office and stairway to cafeteria.

 Carpet loose in library.

 Water damaged ceiling tiles in office off of library and audio visual materials storage room.

lOB Faucet leaking in girls toilet room across from office.

I SB Paint peeling from ceiling in boys toilet room across from the office.

SE Ceiling vent not clean in staff toilet room by the office.

I5B Carpet in bad repair in room # 8, 16 and 17.

18C Door to outside that leads to parking lot and door in gym not tightly sealed across the bottom.

SE Ceiling vents in toilet rooms off of gyms not clean.

6A Ceiling ducts in gym not clean

170 Raw wood support on toilet divider in boys toilet room not cleanable! toilet divider in BAD repair.

19D Combination hand sink drinking fountain in classroom if 14.

15B Carpet in bad repair in Ms. Hunters’ room.

15B Water damaged ceiling tile (and plaster above ceiling tile) in Ms. Hunters’ room.

1 5B Water damaged ceiling tile ( and plaster above ceiling tile) , water leaking from ceiling and carpet in bad repair in room if 18 the computer lab.

1 SB Stage floor in bad repair.

18C Door to outside off of stage not tightly sealed across the bottom.

 


INSPECTION REPORT FOR WRIGHT DENNY ELEMENTARY SCHOOL PERFORMED ON MARCH 9, 2001

6-201.11 Floor tiles in bad repair in the kitchen.

5-203.13 Mop sink not provided for cleaning kitchen and cafeteria.

4-603.13 Cafeteria dining tables not properly washed-rinsed & sanitized.

6-201.11 Hole in wall by 2 vat sink not sealed.


Click for School System's description of physical condition of buildings


GENERAL SANITATION INSPECTION REPORT FOR TA. LOWERY ELEMENTARY SCHOOL PERFORMED ON MARCH 16, 2001

3A Eating utensils being washed in sink in Special Education classroom along with paint brushes and other art supplies.

1 1 A Toxic items stored under sink [lock or child protection devices not used] in Special Education classroom.

l4B Special Education classroom not organized.[ seems to be a lot of clutter]

6A Toaster oven and refrigerator not clean in Special Education classroom. [out-of-date milk, etc.]

6A Floors not thoroughly clean in staff toilet rooms.

 Water damaged ceiling tiles Ms. Albertson’s and D Otto’s classroom.

6A MMT toilet room not thoroughly clean.

18A Ant activity in Primary 1 classroom.

lOB Hot water faucet leaking at hand sink in Primary 1.

6A Desk tops not clean in Primary 1.

1 SB Water damaged ceiling tiles in music room.

 Ceiling tiles not in place in Art storage room.

I 1A Carpeting in hallway by toilet rooms bunching up.

 

INSPECTION REPORT FOR TA. LOWERY ELEMENTARY SCHOOL FOOD SERVICE PERFORMED MARCH 16, 2001

No violations of the WV Food Service Rules noted at the time of the evaluation.