INSPECTION REPORT FOR JEFFERSON HIGH SCHOOL PERFORMED MARCH 19,
2001
15 B Water damaged ceiling tiles in classroom D 5.
5E Ceiling vents not clean in classroom D 6.
18A Termite activity in classroom C 5.
18A Ant infestation throughout the school.
1 7J Soap not provided in men’s toilet rooms throughout the school.
5B Severe problem with smoking in toilet rooms [especially bad in men’s
toilet rooms], ashes on almost all student toilets and air is thickly
contaminated with smoke. Ventilation Systems for toilet rooms do not appear to
be adequate.
5B Excessively hot in classroom C 1.
5E Ceiling ducts not clean in classroom C 18 & C 19.
5E Classroom C 18 & C 19 is very dusty.
5E Air vents in hallway of C section not clean.
Water damaged ceiling tile in
classroom C 13.
6A Carpets do not appear to be cleaned at an acceptable frequency. A
review and follow-up of the written housekeeping schedule may be necessary.
5A Classroom A 26 has discoloration on carpet, that appears to be
related to a mold/mildew problem.
1 5B Water damaged ceiling tile in classroom A 1.
19D Drinking fountains throughout the school are not clean. (they
appear to not have been thoroughly cleaned for days, possible weeks}
SE Ceiling not clean around vents in classroom A 20.
1 5B Water damaged ceiling tiles in classroom A 20.
5E Ceiling vents not clean in toilet rooms.
1 5B Water damaged ceiling tiles in hallway outside of ladies toilet
room in A section.
Sagging ceiling tiles in room A
16.
1 8B Evidence of rodent activity beneath the sink in the teachers
lounge in A section.
Water damaged ceiling tiles in
classroom A 5.
1 5B Classroom C 5 and A 5 have water leaks around back door.
Water damaged ceiling tiles in
hail by classrooms A 13 and A 8.
18C Door to outside by cafeteria not tightly sealed across bottom.
17G More thorough toilet room cleaning needed throughout school.
5E Ceiling vents not clean in toilet rooms in the back of A section.
18B Evidence of rodent activity in classroom A 12.
lOB Sewer gas odor in staff toilet rooms in A section.
18C Door to outside by ramp leading to B section not tightly sealed
across the bottom.
Water damaged ceiling tiles in
hail of B section.
5E Ceiling vent not clean in classroom B 14.
1 5B Water damaged ceiling tiles in classroom B 14 and by entrance to B
12.
1 7G Floor tiles in bad repair in staff toilet rooms in B section.
1 7J Soap and covered trash containers not provided in staff toilet rooms.
15E Plastic cover needed over science sink in the center of classroom B
5.
I IA Outlet safety covers needed on outlet wall strips in classroom B
5.
1 8C Door to outside not tightly sealed in classroom B 10.
lOB Faucet leaking at art sink in classroom B 11.
18C Door to outside not tightly sealed in classroom B 6.
Water damaged ceiling tiles in
Music room, room D 8..
SE Ceiling tiles very dirty, especially around ceiling vents in Music
room, room D 8.
17J Soap not provided in boys locker room, at the hand sinks by the toilet facilities.
I SB Floor tiles in bad repair in the boys locker room.
15E Vinyl torn on massage tables in training room.
1 5B Water damaged ceiling tiles in hall by gymnasium.
17G Floor/wall tiles missing in girls toilet room by cafeteria.
I SB Ceiling in bad repair by entrance to girls toilet room by
cafeteria.
INSPECTION REPORT FOR JEFFERSON HIGH SCHOOL
FOOD SERVICE PERFORMED ON MARCH 19, 2001
There were no violations of the WV Food Service Rules noted at the time
of the evaluation.
Click for School
System's description of physical condition of buildings
GENERAL SANITATION INSPECTION REPORT FOR JEFFERSON HIGH SCHOOL PERFORMED MAY 25, 2001
I 7J Soap dispensers not provided in all student toilet rooms.
1 7G Faucets in bad repair in staff toilet rooms in B section
I 5B Floor/wall molding in bad repair in girls toilet room in section A
15B Ceiling in bad repair in boys and girls locker rooms off of gymnasium.
19C Mixing faucets not provided in boys toilet room off of locker room by gymnasium.
8B Inadequate light in boys shower room.
1 7G Tile cracked in boys shower room.
14B Storage area beside auditorium (by the toilet rooms) not clean and organized.
18C Doors to outside of the building throughout the school not tight fitting ( rodent and insect proof).
SB Smoking in student toilet rooms (much improvement from inspection performed on March 19th but still very much a problem) must be permanently addressed towards providing a sanitary atmosphere in these toilet rooms.
17J Soap and covered trash containers not provided in staff toilet rooms. I 7G Floor/wall tiles in bad repair in several toilet rooms.
Click for School
System's description of physical condition of buildings
GENERAL
SANITATION REPORT FOR CHARLES TOWN JUNIOR HIGH SCHOOL PERFORMED
MARCH 8, 2001
Broken floor tiles in hallway.
I 8C Door to outside not tightly sealed in P. Warner’s computer lab.
18C Door to outside not tightly sealed in room 57 and room 58.
1 5B Water damaged ceiling tiles in room 58.
SB Air conditioning ducts cleaned? There was an odor problem early in
the school year that diminished after the air conditioning system was shut
down..
lOB Faucet dripping from hand sink in boys toilet room across from
cafeteria.
19C Hot water not provided (waterline is shut off) to one hand sink in girl’
toilet room across from cafeteria.
18C Door not tightly sealed across bottom H.Tabeek’s classroom.
170 Toilet dividers in bad repair in boys toilet room in A section.
1 5B Water damaged ceiling tiles in music room.
Serious water damage ceiling
tiles in art room (water laying on light shields) [room 40).
8F Light shields not provided in boys locker room.
1 5G Some of the gym lockers are in bad repair in the boys locker room.
lOB Showerhead dripping in boys locker room.(first one on left).
I 5B Floor in bad repair in toilet room in boys locker room.
I7J Paper towel dispenser empty in toilet room in boys locker room.
lOB Showerhead dripping in girls locker room (second on right).
6A Ceiling vent not clean in girls shower room.
I 7P Covered trash containers (for sanitary disposal) not provided in
toilet room in girls locker room.
I OB Faucets leaking in boys toilet room across from room 30.
I5B Floor tiles in bad repair in both boys and girls toilet rooms
across from room 30.
Water damaged ceiling tiles along
outside wall in classroom #11 and ff13.
11A Smoke detector not working in room # RI.
lOB Faucet leaking in teachers work room (close to exit to portable
class rooms).
I SB Missing floor tiles in storage room off of Mr. Starkeys room.
Water damaged ceiling tiles in
storage room off of Mr. Starkeys room.
Floor/wall molding missing in
room # 25.
INSPECTION REPORT FOR CHARLES TOWN JUNIOR
HIGH SCHOOL PERFORMED ON MARCH 8, 2001
6-201.11 Floor in toilet room in bad repair.
4-501.110 Dish washing machine rinse water temperature not high enough
(machine should register at least 180° F with a plate temperature of at least
165° F; the actual machine reading was 174° F with a plate temperature of 162°
F)
Click for School
System's description of physical condition of buildings
GENERAL SANITATION
INSPECTION REPORT FOR HARPERS FERRY JUNIOR HIGH SCHOOL
PERFORMED ON MARCH 30, 2001
I 5B Water damaged
ceiling tiles in music room.
1 7G More thorough bathroom cleaning needed, especially floors along
walls and around toilets.
1 11A Sagging ceiling tiles in library.
14A More storage space needed in library.
11 A Carpet bunching up in library.
Water damaged ceiling tiles in
upper hallway.
19C Mixing faucets not provided in staff toilet rooms on second floor.
1 5B Water damaged ceiling tile in nurses room..
8F Light shield broken in boys toilet room by cafeteria.
1 SB Water damaged ceiling tiles in girls locker room.
lOB Water leaking from shower head in girls shower room.
1 5B Ceiling tiles in bad repair in boys locker room.
1 7J Soap not provided in toilet room off of boys locker room.
1 8C Door to outside in machine shop not tightly sealed across the
bottom.
15 Paint peeling from ventilation ducts in ceiling of machine shop.
1 7A With the addition of eight classrooms in portable buildings
behind, the school does not have adequate toilet facilities for the schools
population.
158 Water damaged
ceiling tiles in hall leading to cafeteria.
INSPECTION
REPORT FOR HARPERS FERRY JUNIOR HIGH SCHOOL FOOD SERVICE PERFORMED ON MARCH 30
200!
6-201.11 Paint is peeling off of wall over three compartment sink.
4-101. 111 D Counter top by steam table not cleanable.
Click for School
System's description of physical condition of buildings
GENERAL
SANITATION INSPECTION REPORT FOR SHEPHERDSTOWN JUNIOR HIGH SCHOOL PERFORMED MARCH 29,
200l
1 5B Water damaged ceiling tile by door in classroom if 22 and in
classroom if 23.
1 SB Floor tile cracked by outside exit near music room (# 24).
1 5B Floor tile cracked in hallway by classroom # 1.
Ceiling tile sagging in
classroom # 21.
Water damaged ceiling tile in front
corner of classroom if 1.
1 5B Concrete block missing in wall beneath chalk board in classroom if
I.
l SB Water damaged ceiling tile in kitchen area of FACS room.
1 SB Floor in bad repair (not cleanable) in girls toilet room across
from gymnasium.
l 8C Door to outside in machine shop not tightly sealed across the
bottom.
5E Ceiling vent not clean in boys toilet room by gymnasium.
l 5B Wall tiles in bad repair (cracked, not cleanable) in boys toilet
room by gymnasium.
5E Ceiling vent missing cover in hallway by the entrance to the machine
shop.
Floor/wall tiles cracked in
toilet rooms off of locker rooms.
8F Light shield broken in girls locker room.
11A Mirror cracked in boys toilet room off of locker room.
18C Door to outside off of boys locker room not tightly sealed across
the bottom.
8F Light shields not provided in equipment storage room off of
gymnasium.
l70 Handle broken on privacy door to disability access toilet in girls
toilet room across from principals office.
1 9D Inadequate water pressure at drinking fountain in hallway across
from principals office.
Wall in bad repair in stairway
leading to art room.
Paint peeling from ceiling in art room, art storage room, and office off of art room.
Hole in ceiling in storage room
off of art room exposing insulation.
1 7G Tile missing by urinal closest to wall in boys toilet room by
principals office.
170 Handle missing on privacy door to disability access toilet in boys
toilet room by principals office.
1 LA Broken window glass in classroom if 14.
8F Two light shields missing in computer lab.
1 5B Water damaged ceiling tile in computer lab.
INSPECTION
REPORT FOR SHEPHERDSTOWN JUNIOR HIGH SCHOOL FOOD SERVICE PERFORMED MARCH 22,
2001
6-201. 1 1 Ceiling tiles discolored around hood.
4-102.111 Utensil holders on serving line in bad repair.
4-601.11 1 Interior of walk-in refrigerator no clean ( white mold-like
growth).
6-201.12 Wall around duct in storeroom not sealed.
5.501. 110 Inadequate dumpster capacity for garbage storage.
Click for School
System's description of physical condition of buildings
GENERAL
SANITATION INSPECTION REPORT FOR BLUE RIDGE ELEMENTARY SCHOOL PERFORMED MARCH 27,
2001
Water damaged ceiling tile in
toilet room in classroom if 14.
1 IA Over stocked shelf over coat rack in classroom # 14.
6A Ceiling tiles not clean around air ducts in classrooms # 14 & if
6.
1 SB Water damaged ceiling in the larger portable classroom.
I4A Toilet room not operational, used for storage, in the larger
portable classroom.
I 8C Door to outside not tightly sealed in the portable classroom with
the brick facing.
Water damaged ceiling tiles in
classrooms # 1& # 4.
18A Ant activity in cafeteria dining area.
1 5B Ceiling water damaged by vent, in boys toilet room in upper
hallway near cafeteria.
1 SB Water damaged ceiling tiles in hallway leading to cafeteria.
Missing ceiling tiles, exposed
insulation in classroom # 7.
1 8A Food products stored in classrooms should be stored in glass,
metal, or plastic air tight containers.
I5B Water damaged ceiling tiles by entrance to classroom # 6.
Paint peeling from brick wall
in boys toilet room by gymnasium.
l7J Soap not provided in boys toilet rooms.
19D Drinking fountain not clean by gymnasium.
l5B Paint peeling from wall in girls toilet room by utility room with
chlorinator.
1 SB Ceiling tiles missing, water damaged in boys toilet room by
utility room with chlorinator.
1 7G Urinal privacy barrier badly corroded in boys toilet room by
utility room with chlorinator.
SE Ceiling vent not clean in classroom ft 4.
1 8C Door to outside not tightly sealed in library.
Water damaged ceiling tiles in
library and office off of library.
1 SB Missing ceiling tile and water damaged ceiling tile in hallway by
office.
15E Window blinds in bad repair in classroom # 24.
1 5B Water damaged ceiling tiles in classroom ft 24.
18C Door to outside (old main entrance) not tightly sealed across the
bottom.
18C Door to outside (to staff parking lot) not tightly sealed across
the bottom.
1 5B Water leaking onto electrical conduit and light fixtures in
classroom if 21.
lOB Water leaking from faucet in sink in classroom # 21.
SE Heating units on wall not clean in classroom if 21.
1 8C Door to outside by dumpster not tightly sealed across bottom.
Water damaged ceiling tile in
hallway by classroom # 32.
INSPECTION REPORT FOR BLUE RIDGE ELEMENTARY
SCHOOL FOOD SERVICE PERFORMED MARCH 27, 2001
4-101.111 Laminate in bad repair on front of serving line.
Click for School System's description of physical condition of buildings
GENERAL
SANITATION INSPECTION REPORT FOR NORTH JEFFERSON ELEMENTARY SCHOOL PERFORMED MARCH 13, 2001
4C Dumpster lid broken, laying on the ground.
Floor in bad repair in women’s
staff toilet room
lOB Seal appears to be leaking on toilet in women’s staff toilet room.
19C Mixing faucet not provided in staff toilet rooms.
19D Drinking water dispenser not clean in staff lounge (west end of
building)
6A Microwave oven in classroom #25 not clean
I 5B Tile broken-up along back wall in classroom if 6.
1 G & I E Cat in classroom #19, does cat have up to date rabies
vaccination? The room smells like a dirty litter box.
SE Older wall heating units not clean
l 7G More thorough cleaning needed in toilet rooms.
6A More storage area needed for janitorial supplies, some are being
stored in the hallway.
Hole in ceiling tile in hallway
leading to classrooms #30 and ff31.
I 7J Paper towels not provided in boys toilet room on west end of
building.
5G Panel off of heat unit in art room, appears to be malfunctioning.
8 F Unshielded light fixture over ice cream freezer.
5 E Air ducts not clean in gym.
19 D Water fountain not clean in gym
6 A Acoustical wall panels not clean in gym.
18 C Door to outside not tightly sealed across the bottom in gym.
Water damaged ceiling tile in
computer room.
1 SC Door to outside across from computer lab
not tightly sealed across the bottom.
18 C Door to outside not tightly sealed
across the bottom in classroom # 10.
I S B Floor tile in bad repair and wall tile cracked in boys toilet
room in the east end of building.
5 E Ceiling vents not clean in classroom if 4. (Especially bad over
activity rug)
18 A All food products ( animal and human) stored in classrooms must be
stored in air tight metal, glass or plastic containers to prevent insect and
rodent infestation.
11 A Glass broken on door in hallway by large fish tank.
INSPECTION REPORT FOR NORTH JEFFERSON
ELEMENTARY SCHOOL FOOD SERVICE PERFORMED MARCH 13, 2001.
3-302.11 Raw hamburger stored over uncovered dishes of jello.
3.401. 11 Temperature recording logs not
kept.
6-501.14 Ceiling vent over dish machine not clean.
Click for School System's description of physical condition of buildings
GENERAL
SANITATION INSPECTION REPORT FOR PAGE JACKSON ELEMENTARY SCHOOL
PERFORMED MARCH 15, 2001
6A Floors in kindergarten toilet rooms not thoroughly clean.
I 7G Urinal stall divider in bad repair in men’s toilet room.
19C Mixing faucets not provided in some of the toilet rooms in the
school
1 9C Hot water not provided in student toilet rooms (it is turned off
due to concern about hot water burns)
I5B Water damaged ceiling tile from ceiling leaks in MMI classroom.
1 SB Water damaged ceiling tiles from ceiling leaks in girls toilet
room near cafeteria.
1 8C Door to outside not tightly sealed in hallway used for new book
storage.
l4A More storage space needed for classroom supplies.
I5B Water damaged ceiling tiles in classroom # 17, if 20 & Ms.
Potters’ room.
17G Floor/wall molding in bad repair in music room.
INSPECTION REPORT FOR PAGE JACKSON ELEMENTARY
SCHOOL FOOD SERVICE PERFORMED MARCH 15, 2001
6-201.11 Water damaged ceiling tile in storeroom.
5-205.15 Mop sink water faucet leaking.
4-501.11 Excessive ice build-up in walk in freezer.
Click for School
System's description of physical condition of buildings
GENERAL SANITATION INSPECTION REPORT
FOR RANSON ELEMENTARY SCHOOL PERFORMED MARCH 28, 2001
19C Hot water for hand washing not provided in staff toilet room by
cafeteria.
19C Hot water not provided for hand washing in student toilet rooms in
main hallway.
1 SB Paint peeling from wall in girls toilet room by cafeteria.
5E Filter not clean on window unit air conditioner in Ms. Schnablys’
classroom.
I SB Ceiling tile missing by door to boys toilet room by cafeteria.
3A Turtles in Ms. Marcums’ classroom require that a written plan be provided
and implemented for proper sanitary handling and hand washing procedures.
I SB Water damage on ceiling around vent in hallway outside Ms.
Marcums’ classroom.
SF Light shield missing in room used for storage of ice cream and
popcorn makers.
1 SB Water damaged ceiling tiles leading to gymnasium.
I 8C Door to outside not tightly sealed in Pre K classroom.
I SB Water damaged ceiling tiles by coat hooks in Ms. Thompsons’
classrooms and in Ms. Toothmans’ classroom.
18C Door to outside not tightly sealed in Ms. Costellos’ classroom.
6A Utility sinks in maintenance closets not clean.
Loose ceiling tile in boys’
toilet room leading to gymnasium.
Water damaged ceiling tiles in
Councilors office.
6A Ceiling not clean in gymnasium by basket ball net closest to the
music room.
I 8C Doors to outside in gymnasium not tightly sealed across the
bottom.
8F Damaged light shield in Mr. Sherwoods’ classroom.
4 portable classrooms.
INSPECTION
REPORT FOR RANSON ELEMENTARY SCHOOL FOOD SERVICE PERFORMED MARCH 28, 2001
6-201.1 I Paint peeling from wall over dish machine.
6-201.11 Floor/wall molding loose .around steam kettle
drain
6-201. 1 1 Wall in bad repair, plaster broken up and not sealed around
the plumbing, below the dish machine.
Click for School System's description of physical condition of buildings
GENERAL
SANITATION INSPECTION REPORT FOR SHEPHERDSTOWN ELEMENTARY SCHOOL
PERFORMED MARCH 26, 2001
18A Food stored in classrooms should be stored in metal, glass, or
plastic air tight containers.
I SB Water damaged ceiling tiles over coat hooks in classroom if 11
& #8.
I4A Toilet room used for book storage in classroom ft 9.
I 5B Water damaged ceiling tiles in classroom #9.
14A Cabinet needed for sanitary storage of food in classroom #9.
14A Laminating machine stored in hallway.
1-5B Ceiling tiles in hallway by lockers badly discolored.
14A More organization of teaching supplies needed in Ms. Lawrences’ classroom.
I SB Hole in ceiling tile by vent in Ms. Lawrences’ classroom.
1 8C Door to outside not tightly sealed across bottom in library &
in hallway leading to playground.
I 7G More thorough floor cleaning needed in student restrooms along the
floor/wall
junctions.
I 5B Material covering ceiling in gymnasium loose [coming off in
patches], not cleanable.
5E Heating units [wall units] in gymnasium not clean and in bad repair.
1 5B Floor tile missing in gymnasium.
Floor/wall molding missing in
gymnasium.
1 SB Water damaged ceiling tile by electrical panel in storage room off
of gymnasium.
I5B Floor! wall tile cracked in boys toilet room in back of school.
SE Exposed insulation visible in Ms. Walters classroom ceiling vent.
5A Several classrooms have vents that are covered with tape.
Floor/wall molding missing in
classroom # 19.
INSPECTION REPORT FOR SHEPHERDSTOWN
ELEMENTARY SCHOOL FOOD SERVICE PERFORMED MARCH 26, 2001
6-501.12 Ceiling vent not clean in storage room over
freezer.
4-602.13 Ice maker filter not clean.
6-50 1.11 Water damaged ceiling tile over 3
door refrigerator not accurate.
6-501.11 Loose ceiling tile over 3 door refrigerator.
4-203.11 Thermometers on the two 3 door refrigerators
not accurate.
4-101.1 ID Wood shelves for cleaning supplies not sealed [paint, varnish, polyurethane, etc.]
Click for School
System's description of physical condition of buildings
GENERAL SANITATION
INSPECTION REPORT FOR C.W. SHIPLEY ELEMENTARY SCHOOL
PERFORMED MARCH 14, 2001
17G Toilet room fixtures not thoroughly cleaned (base of toilets and
hand washing sinks).
1 SB Water damaged ceiling tiles in staff toilet rooms.
IOA Mixing faucets not provided in staff toilet rooms.
17G Floors not thoroughly clean in staff toilet rooms.
Water damaged ceiling tiles in
kindergarten.
I5B Water damaged ceiling tiles in hallway off of kindergarten.
SE Ceiling vents not clean in classroom if 10.
Water damaged ceiling tiles in
classroom #10.
Ceiling tile loose over coat
hooks in classroom #9.
Ceiling tile not in place
(exposed insulation) in classroom ft 11.
1 SB Water damaged ceiling tiles around ceiling vent in room # 11.
l4A Inadequate room for storage of school supplies (possibly some
supplies that are no longer used could be discarded).
1 5B Water damaged ceiling tiles in hall immediately above entrance to
classroom #13.
18C Door to outside leading to parking lot not tightly sealed across
bottom.
6A Classroom floors do not appear to be receiving regular, thorough
cleaning.
6B Upon request, received a copy of the schools cleaning schedule.
Could it be adjusted to allow for more thorough floor and toilet room cleaning
? (Ex. 11:45-1:20 help students dump lunch trays, couldn’t teachers help with
this? Then toilet rooms could be cleaned during the day, since they are cleaned
only at 6 PM and often the school is used late in the evening. Also, on one
schedule 1 hour is allotted to vacuum 4 rooms and on another schedule 25
minutes allotted for vacuuming 7 classrooms and wet mopping the modular class
room floor).
19D Drinking fountains not clean.
1 9G Interior of icemaker not clean.
1 5B Water damaged ceiling tile in computer lab.
18C Door to outside not tightly sealed in classroom # 20, #21 & if
24.
I 8C Door seal in bad repair in room if 18.
1 SB Water damaged ceiling tiles in classroom # 24 & ft 27.
19F Cup dispensers not used in classroom # 24.
Loose ceiling tile in classroom
# 25.
ISA Ant activity along wall in room ft 27.
6A Sink and counter not clean in room # 28.
17J Soap not provided in boys’ toilet room.(end of building closest to
the basket ball court)
5E Ceiling vent not clean in boys toilet room.(end of building closes
to the basket ball court)
1 8C Doors to the outside leading to the basket ball hoops not tightly
sealed across the bottom.
l7G Floors not clean in toilet rooms by gym.
19D Water fountain in gym not clean.
SE Exposed insulation around air duct return in portable class room.
1 SB Floor tile cracked in gym along wall.
1 SB Broken ceiling tiles along serving line in kitchen.
INSPECTION REPORT FOR C.W. SHIPLEY ELEMENTARY
SCHOOL FOOD SERVICE PERFORMED MARCH 14, 2001
6-202. iS Back screen door not tightly sealed across bottom.
6-201.1 1 Wall tile cracked behind 2 vat sink.
4-201.1 1 More freezer storage space needed.
Click for School
System's description of physical condition of buildings
SCHOOL SYSTEM
LETTER CONCERNING LEAD & PESTICIDES AT SOUTH JEFFERSON ELEMENTARY
SCHOOL
June 5, 2001
Dear Parents/Guardians:
As many of you
know, there were a number of questions raised by parents and staff regarding
the water quality and other health concerns at South Jefferson Elementary
School As a result of these questions, several things have been done that we
believe answer many of the questions presented. We would like to use this
opportunity to update you and to let you know of projects that should be
completed this summer.
The following
has occurred:
The
Jefferson County Health Department, the Regional Office of the West Virginia Health Department, the
West Virginia University Extension Service - Jefferson County Office, the West Virginia Department of Agriculture and administrative staff from
the Jefferson County Board of Education Office have been involved in the
assessment process.
All water tests required by the West Virginia
Health Department have continued on a regular basis and currently meet
standards.
The West Virginia Department of Agriculture
tested the soil for pesticides with no findings.
Reviews of aerial photos of the land taken
prior to construction of the school indicated that the land was used as
pasture. Research did not indicate that the land was used in a manner that
would cause concern.
Bottled water was provided.
The water treatment plant has been upgraded
as per recommendation by the West Virginia Department of Health and is
currently in operation with the new treatment system.
The system is flushed daily at each point
where consumption may occur.
Summer plans
include:
• An
assessment of the transformer by Allegheny Power.
• Pipes
and fixtures replaced in classrooms where higher than normal lead levels have
occurred in the past.
We want to assure you that currently water
tests indicate that all levels meet approved standards. The activities planned
for the summer are being completed only as a precaution and to assure that
elevated lead levels do not occur in the future. Much has been learned by this
process and, as a result, I believe that there will be better communication
among the agencies.
All reports of tests administered this year
are available in the Principal*s Office. Mrs. VanCamp will be glad to share those
with you. Questions that cannot be answered at the school can be directed to
Beverly Hughes, Associate Superintendent (728-9228), John Norman, Coordinator
of Facilities and Maintenance (728-9215) or George Frame, Director of Support
Services (728-9241).
Sincerely,
Beverly Hughes
Associate Superintendent
GENERAL
SANITATION INSPECTION REPORT FOR SOUTH JEFFERSON ELEMENTARY SCHOOL PERFORMED
APRIL 13, 2001
I SB Carpet in library is shredding at seams.
Tile is broken up by HVAC
system in art room.
1 IA Shelves over coat hooks overburdened in Ms. Mahoney’s classroom.
I IA Ceiling tile not tight fitting over sink in Ms. Mahoney’s
classroom.
6A Light shield not clean in Ms. Woodburn’s classroom.
I 7G More thorough toilet room cleaning needed, especially floors.
I lA Ceiling tile not tight fitting in Ms. Batson’s classroom.
ISB Water damaged ceiling tiles in classroom if 7.
11A Ceiling tile not tight fitting (exposed insulation) in classroom #
IS.
SE Filter not clean in wall HVAC system in Ms. Kees’ classroom.
Water damaged ceiling tiles
over sink in Ms. Kees’ classroom.
l5B Water damagçd ceiling tile in Ms. Cloud’s classroom.
19F Cup dispenser not used in Ms. Fincham’s classroom.
Water damaged ceiling tiles in
Ms. Fincham’s classroom.
4B Inadequate garbage storage facilities.
I 1A Ceiling tile not tight fitting in Ms. Greenfields’ classroom.
I 1A Shelves over coat rack overburdened in Ms. Greenfields’ classroom.
I IA Ceiling tiles not tight fitting in Ms. Whittingtons’ classroom.
8F Light shield missing in classroom # 14.
1 1A Ceiling tile not tight fitting in classroom # 14.
1 7G Floor not cleanable in boys toilet room where old toilet dividers
were anchored.
1 7J Two soap dispensers missing in girls toilet room on south end of building.
I SB Floor tiles cracked in hallway along
intersection leading to Ms. Clouds’ classroom.
I 5B Floor/wall molding loose and in bad
repair in numerous classrooms.
6A Portable stage not clean in music room.
11 A Shelf over coat hooks overburdened in
classroom # 24.
I 5B Water damaged ceiling tile around smoke detector in hallway by Ms.
Clouds’ classroom.
170 Boys toilet room door not tight fitting on south end of building.
6A Carpet not clean in classroom if 20 and #21.
1 1 A Ceiling tile not tight fitting in classroom #20.
1 1A Shelf over coat rack overburdened in Mr. Marmorellas’ classroom.
INSPECTION REPORT FOR SOUTH JEFFERSON
ELEMENTARY FOOD SERVICE PERFORMED ON APRIL 13, 2001
Inadequate freezer storage space provided for current food ordering system.
Click for School
System's description of physical condition of buildings
GENERAL SANITATION
INSPECTION REPORT FOR WRIGHT DENNY ELEMENTARY SCHOOL PERFORMED
ON MARCH 9, 2001
lOH Mop sink not provided for kitchen and cafeteria area.
Water damaged ceiling tile in
hallway between office and stairway to cafeteria.
Carpet loose in library.
Water damaged ceiling tiles in
office off of library and audio visual materials storage room.
lOB Faucet leaking in girls toilet room across from office.
I SB Paint peeling from ceiling in boys toilet room across from the
office.
SE Ceiling vent not clean in staff toilet room by the office.
I5B Carpet in bad repair in room # 8, 16 and 17.
18C Door to outside that leads to parking lot and door in gym not
tightly sealed across the bottom.
SE Ceiling vents in toilet rooms off of gyms not clean.
6A Ceiling ducts in gym not clean
170 Raw wood support on toilet divider in boys toilet room not cleanable!
toilet divider in BAD repair.
19D Combination hand sink drinking fountain in classroom if 14.
15B Carpet in bad repair in Ms. Hunters’ room.
15B Water damaged ceiling tile (and plaster above ceiling tile) in Ms.
Hunters’ room.
1 5B Water damaged ceiling tile ( and plaster above ceiling tile) ,
water leaking from ceiling and carpet in bad repair in room if 18 the computer
lab.
1 SB Stage floor in bad repair.
18C Door to outside off of stage not tightly sealed across the bottom.
INSPECTION REPORT FOR
WRIGHT DENNY ELEMENTARY SCHOOL PERFORMED ON MARCH 9, 2001
6-201.11 Floor tiles in bad repair in the kitchen.
5-203.13 Mop sink not provided for cleaning kitchen and
cafeteria.
4-603.13 Cafeteria dining tables not properly
washed-rinsed & sanitized.
6-201.11 Hole in wall by 2 vat sink not sealed.
Click for School System's description of physical condition of buildings
GENERAL
SANITATION INSPECTION REPORT FOR TA. LOWERY ELEMENTARY SCHOOL PERFORMED ON MARCH 16, 2001
3A Eating utensils being washed in sink in Special Education classroom
along with paint brushes and other art supplies.
1 1 A Toxic items stored under sink [lock or child protection devices
not used] in Special Education classroom.
l4B Special Education classroom not organized.[ seems to be a lot of
clutter]
6A Toaster oven and refrigerator not clean in Special Education
classroom. [out-of-date milk, etc.]
6A Floors not thoroughly clean in staff toilet rooms.
Water damaged ceiling tiles Ms.
Albertson’s and D Otto’s classroom.
6A MMT toilet room not thoroughly clean.
18A Ant activity in Primary 1 classroom.
lOB Hot water faucet leaking at hand sink in Primary 1.
6A Desk tops not clean in Primary 1.
1 SB Water damaged ceiling tiles in music room.
Ceiling tiles not in place in
Art storage room.
I 1A Carpeting in hallway by toilet rooms bunching up.
INSPECTION REPORT FOR TA. LOWERY ELEMENTARY
SCHOOL FOOD SERVICE PERFORMED MARCH 16, 2001
No violations of the WV Food Service Rules noted at the time of the evaluation.